Improved Testing Method Using the Multi-Transformers Synthetic Circuit to Verify Capacitive Charging Current Switching Capability of High-Voltage Circuit Breakers

oleh: Yun-Seong Kim, Jong-Hyuk Choi, Rahul S. Patil, Min-Won Park

Format: Article
Diterbitkan: MDPI AG 2023-06-01

Deskripsi

To perform a capacitive current switching test (CCT) at AC extra-high-voltage (EHV) and above level, this paper proposes a new multi-transformer synthetic circuit (MTSC) test method that replaces the general synthetic test method using capacitor banks. An MTSC method has a simpler circuit structure compared to other synthetic testing methods and has higher equivalence (especially recovery voltage and <i>TRV</i>) and validity. Using this method, CCTs for circuit breakers (CBs) of the AC 420 kV voltage class were performed as a field test using the IEC 62271-100 standard. To verify that the test method was valid, test results were analyzed and compared with the requirements of a standard. Consequently, the MTSC method completely covered the requirements of the standard.