Effect of Ground Electrodes on the Susceptibility to Damage of Customer Premises Equipment (CPE) under Impulse Conditions
oleh: Usman Muhammad, Normiza Mohamad Nor, Annuar Mohd Ramli, Nurul Nadia Ahmad
Format: | Article |
---|---|
Diterbitkan: | MDPI AG 2022-02-01 |
Deskripsi
One of the requirements for the safe operation of customer premises equipment (CPE) is an adequate grounding system as a means to divert high fault currents to the ground. In this work we report on the results of an experimental study of the impulse characteristics at a charging voltage of 30 kV on the surge protective device connected to 16 earth electrodes and installed at two sites, giving various ground resistance at low voltages, R<sub>DC</sub> values. All of these grounding electrodes were installed and tested under the same charging voltage to determine the effectiveness of ground electrodes toward the damage of a modem at the premises. We observed that modems did not experience damage when the ground electrode of the distribution pole (DP) had an RDC below 30 Ω in general and below 46 Ω when ground electrodes installed in low resistivity soil were used. The impulse polarity did not affect the damage susceptibility of the CPE.